Task: | Data Collection |
---|---|
Structure: | Combination |
Mathematical Model: | Data Transmisson |
Signal: | Continuous |
Function: | Automatic Control, Data Collect and Transmission |
Certification: | ISO: 9001, CE |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Remote I/O system CN-8013 Network Adapter for CC-Link protocol (Bus coupler)
ODOT CN-8013 CC-Link Network Adapter
Module Overview
CN-8013 CC-Link network adapter supports standard CC-Link Ver.2 communication and it could monitor the communication status of IO modules in real time.
Hardware Specification
Power Consumption:110mA@24Vdc
Internal Bus Supply Current:Max: 2.5A@5Vdc
Isolation:System Power to Field Power Isolation
Power Supply:Nominal:24Vdc, Range:22-28Vdc
Field Power Current:Max. DC 8A
IO Modules Supported:32pcs
Wiring:Max.1.5mm²(AWG 16)
Mounting Type:35mm DIN-Rail
Size:115*51.5*75mm
Weight:130g
Environment Specification
Operational Temperature: -40~85ºC
Operational Humidity: 5%-95% (No Condensation)
Protection Class: IP20
CC-Link Parameter
Protocol CC-Link Ver.2
Station Type Remote device station
Number of Logical
Stations Occupied 1, 2, 3, 4
Extended Loop Setup 1 time, 2 times, 4 times, 8 times
I/O Data Capacity RX/RY capacity( bit) max. 896
RWr/RWw capacity( word) max. 128
Baud Rate 156K/625K/2.5M/5M/10Mbps
Node Station (Station No.)
1~64(DIP switch configuration), when DIP switch
value is not 1~64, and the mandatory station number is 1.
Interface 5 Pin screw terminal
Max. bus length 1200m( 156kbps)
Terminal resistance 120ohm
Installation
DIN Rail
Wiring
Suppliers with verified business licenses